DATRAN XL4 RTU – Owners Manual – v1.1 June 2012
www.qtech.co.nz Page 11
Note In electrically noisy environments it is necessary to use screened data cable and keep the cable length as
short as possible.
Function
Pin 1
DTR
Pin 2
RTS
Pin 3
CTS
Pin 4
Ground
Pin 5
RXD
Pin 6
TXD
Pin 7
DCD
Pin 8
RI
Note. RJ45 cable connector pin numbering
RS232 – RJ45 Connections
In general the RS232 serial port can be extended up to a maximum of 15 metres. Beyond this distance
communications will be unreliable.
USB
USB USB
USB Configuration
ConfigurationConfiguration
Configuration Port
Port Port
Port
The Configuration Port is used for on-line configuration, diagnostics and data/program exchange. The port is also
used for I.C.P. (In circuit programming) of the system firmware.
The port is labelled “CNFG” on the XL4 and uses a Type A to Type B USB cable. Maximum cable length is 5
meters.
The configuration and software upgrade of the Q04 ARM Processor is detailed in a separate manual.
Ethernet Port
Ethernet PortEthernet Port
Ethernet Port
This is a 10/100 MBit Ethernet port labelled “ETH” on the XL4.
This port can be used for Base Station or peripheral communications via such protocols as QComms, DNP3,
Modbus Slave/Master, etc. The Ethernet socket has a green and an orange LED. The orange LED is the Link
LED and turns on when a good link is established then flashes off for Ethernet traffic. The green LED is the Speed
LED and turns on for 100 MBit connections and off for 10 MBit connections.
Comentários a estes Manuais